Description
The ML100.200 is a simple and cost effective approach to convert the AC voltage of a typical three phase system into a regulated DC voltage. It only requires two phases and thereby saves terminal space, terminal cost, wires, fuses and installation time.
The ML100.200 is very compact, high efficient and easy to use. The input is internally protected, which makes external fuses unnecessary in many cases. Weighing only 360g, it is a lightweight compared to the 50/60Hz control transformers, which are commonly used for low-power control voltages where a neutral wire is not available. High immunity to transients and power surges as well as low electromagnetic emission makes usage in nearly every environment possible.
You can place an order for the PULS ML100.200 DIN-rail Power supply online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.
Specification
Input Data | |
---|---|
AC-Input Voltage | AC 380-480V (± 15%) |
DC-Input Voltage | - |
EN61000-3-2(PFC-Norm) | fulfilled |
Power Factor | 0.6 |
Input Inrush Current Limitation | NTC |
Peak turn on current | 30A/36A |
External Input Fuse Recommendation | min. B-10A / C-6A |
Output Data | |
nominal Voltage | 24Vdc |
Adjustment Range | 24-28V |
Output Current Range | 4.2-3.6A |
Output Current | 3.6A at 28V, 4.2A at 24V |
Output Power | 100W |
max. Ripple and Noise Voltage | 50mVpp |
Physical Characteristics | |
Mounting | DIN-Rail |
Dimension | 73mm x 75mm x 103mm |
Weight | 360g |
Operating Temperature | -10°C ... +70°C |
General | |
Derating | 2.5W/° at >+60°C |
Efficency, typ. | 89.5% |
Power Losses, typ. | 11.7W |
MTBF | 1.594.000h |
Connection method | Spring-clamp terminals |
E Classification | eClass 5.1 27049002, eClass 6.x 27049002, eClass 7.x 27049002, eClass 8.0 27049002, eClass 9.0 27040701, ETIM 4.0 EC000599, ETIM 5.0 EC002540, HS Code HS 85044082 |
Package Checklist | |
Packaging Unit | 1pc |