Beijer BFI-E2-12-0023-1F1Y Frequency inverter
- Output power 0.37 kW
- Output 3x230 VAC, 2.3 A
- Input voltage 1x230 VAC
- IP66
- Brand: BEIJER
- Product Code: BFI-E2-12-0023-1F1Y
Description
BFI E2 inverters offer general-purpose drive facilities, dedicated to low-power applications, combining innovative technology, reliability, robustness, and ease of use. Dust-tight and ready for wash-down, the IP66-rated inverters can be mounted directly on your processing equipment. The IP20-rated inverters can be mounted in control cabinets or in machine parts providing the required protection.
Enjoy the ease of online inquiries for
the Beijer BFI-E2-12-0023-1F1Y Frequency inverter. You can submit your inquiry on our website and get the most friendly
communication with our experts to choose high-quality industrial automation
products at a reasonable price from our Middle East branches (UAE (Dubai), KSA
(Al Khobar, Riyadh), and Oman).
Specification
Output ratings | |
---|---|
Output voltage | 3 x 230 VAC |
Rated motor current | 2.3 A |
Overload capacity | 150% for 60 seconds, 175% for 2 seconds |
Output frequency | 0 – 250Hz, 0.1Hz resolution |
Input ratings | |
Supply voltage | 200 – 240VAC ± 10% |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Communication | |
Modbus RTU | 9.6 - 115.2 kbps selectable (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | |
Modbus TCP | |
Ethernet IP | |
EtherCat | |
Profinet IO | |
Profibus DP(DPV1) | |
Device Net | |
CC-Link | |
CAN open | |
Display | |
Programmable display | |
Multi language OLED display | |
External OLED display | |
LED display | |
HVAC | |
PID-control | PI-control with sleep/wake up |
Spin start | |
Pump dry protection | |
Stir function | |
Motor pre-heat | |
Broken impeller and broken belt detection | |
Bypass control | |
Fire mode | |
Control terminals | |
Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
Inputs | 4 in total, 2 Digital, 2 Analog or Digital, selectable |
Digital inputs | 8-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 6A AC, 5A DC |
Analog outputs | 0 to 10 Volt, 0 to 20mA, 4 to 20mA |
Outputs | 2 total, 1 relay, 1 analog or digital |
Standard compliances | |
Conformance | CE, UL |
Marine approvals | |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Physical Characteristics | |
IP class | IP66 |
Physical size | Size 1 |
Measurements (H x W x D) | 232 mm x 161 mm x 179 mm |
Weight | 3.1 kg |
Built in Main switch, control switch and potentiometer | |
Conformal coated PCBs | |
Operation temperature | -10 to 40 °C |
Humidity | 95% max, non-condensing |