- 85 to 264 VAC, 120 to 370 VDC Input power range
- 24 VDC (40 W) Output power range
- DIN-rail mounting
- -20 to 70°C operating temperature range
- Brand: MOXA
- Product Code: MDR-40-24
Description
The MDR Power Supply Series supports inrush current protection of 30 A at 115 VAC and 60 A at 230 VAC. The series has an operating temperature range of -20 to 70°C and a three-year warranty, which ensures suitability for operating in harsh environments. In addition, the MDR Series has passed a 100% full load burn-in test, is UL/CUL listed, TÜV/CB certified, and CE marked. There are also models available with output ratings from 40 W to 60 W with 24 VDC output.
You can also find the MDR-60-24 model in the Power supplies.
You can Buy the MOXA MDR-40-24 DIN-rail Power Supply via inquiring online at a competitive price in the Middle East (UAE (Dubai), KSA (Al Khobar, Riyadh), and Oman). Enjoy the cost-effective shipping options at a specific time in your location.
Specification
Power Requirements | |
---|---|
Input | Voltage: 85 to 264 VAC (47 to 63 Hz), 120 to 370 VDC; Typical Current: 0.7 A @ 230 VAC, 1.1 A @ 115 VAC; Typical Current (cold start): 60 A @ 230 VAC, 30 A @ 115 VAC |
Operating Voltage | - |
Output | Wattage: 40 W; Voltage: 24 VDC; Current Rating: 0 to 1.7 A |
Over-voltage Protection | 31.2 to 36 V (Shut down operating voltage, repower on to recover) |
Overload Protection | 105 to 150% (Constant current limiting, recovers automatically after fault condition is removed) |
Reverse Polarity Protection | - |
Physical Characteristics | |
Dimensions | 40 x 90 x 100 mm (1.57 x 3.54 x 3.94 in) |
Housing | - |
Weight | 260 g |
Ambient Relative Humidity | 20 to 90% (non-condensing) |
Operating Temperature | -20 to 70°C (-4 to 158°F) |
Storage Temperature | - |
Installation | DIN-rail mounting |
Standards and Certifications | Safety: UL 508, EN 62368-1, IEC 62368-1; EMC: EN 55032/35, EN 61000-3-2 Class A, EN 61000-3-3, EN IEC 61204-3, EN IEC 61000-6-2; EMS: IEC 61000-4-2 ESD: Contact: 4 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 2 kV, IEC 61000-4-5 Surge: Power: 4 kV, IEC 61000-4-6 CS: 0.15 kHz to 80 MHz: 10 Vrms, IEC 61000-4-8 PFMF: 30 A/m, IEC 61000-4-11 |
MTBF | - |
Supported Series | |
Supported Series | - |