Easy World Automation | Westermo PS-100 DIN-rail Power Supply

Westermo PS-100 DIN-rail Power Supply

  • DIN-Rail PoE Ready PSU
  • 48 – 56 VDC (adj. by front panel potentiometer)

Description

The PS-30 is a DIN-rail power supply unit (PSU) complying with many major safety approvals. The robust plastic housing makes the PSU small and the fine ventilation grid prevents small items entering and damaging it. The operational temperature range –10°C to +70°C and output voltage 24 VDC at 1.3 A makes the unit ideal for many industrial applications.

The PS-30 can be mounted and connected in record time as no tools are required for the spring clamp terminal connections.


You can place an order for the Westermo PS-100 DIN-rail Power Supply online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.

Specification

Input
Input voltage AC 100 – 120 / 220 – 240 V (Auto Select), 47 to 63 Hz (AC 85 to 132 V / AC 184 to 264 V, DC 220 to 375 V)
Input current <2.1A (@ AC 100 Vin, 100 W Pout), <1A (@ AC 220Vin, 100W Pout)
External Fusing Unit provides an internal fuse (T3A15H, not accessible)
Transient immunity Transient resistance acc. to VDE 0160 / W2 (750 V / 1.3 ms), over the entire load range
Hold-up time >40 ms @ AC 230 V, 48 V / 2.1 A >20 ms @ AC 196 V, 48 V / 2.1 A >20 ms @ AC 100 V, 48 V / 2.1 A
Output
Output voltage 48 – 56 VDC (adj. by front panel potentiometer) 48 V ± 0.5% @ 2.1 A
Voltage regulation stat. <1% Vout (Jumper in pos. 'Single Use') stat. <3% Vout (Jumper in pos. 'Parallel Use'), dyn. ±1.5% Vout over all
Overvoltage prot <60 V
Protection Unit is protected against (also permanent) short circuit, overload and open-circuit
Derating Depending on the built-in orientation
Power back immunity 63 V
Physical Characteristics
Ambient temperature range (measured 25 mm below unit)
Storage temperature –25°C to +85°C (–13 to 185°F)
Operating temperature –10°C to +70°C (14 to 158°F)
Humidity max. 95% (without condensation)
Electromagnetic emissions (EME) EN 61000-6-3 (includes EN 61000-6-4), Class B (EN 55011, EN 55022), EN 61000-3-2 (PFC)
Electromagnetic immunity (EMI) EN 61000-6-2 (includes EN 61000-6-1)