Description

Data and energy:

The primary switched mode DIN rail power supply SLA4.100 specifically supplies AS Interface® systems with energy. The AS-Interface bus technology allows to connect up to 62 participants to a control and to supply them with energy with a single two-conductor cable. When connecting slaves, the yellow AS-Interface cable offers the high degree of protection IP67 in conjunction with the insulation displacement. The communication signals of the individual network participants are modulated onto the supply voltage. For this purpose, specific power supply units with integrated data decoupling are required for AS-Interface systems.

Fast addressing of slaves:

The "IR addressing mode" selectable via jumper interrupts the data communication on the yellow AS-Interface cable. Participants with an infrared interface can then quickly be assigned a new ID address by means of an infrared programming unit without the need to disconnect them from the AS-Interface cable. Afterwards, the "Communication Mode" can be selected again to restart the data communication.

Worldwide operation:

This compact primary switched-mode built-in power supply can be operated on all usual single-phase line voltages. Its design corresponds to international standards. The CE-Declaration allows for industrial and office application.

Ground fault detector:

Acc. to EN60204 part 1 and DIN VDE0113 respectively, ground faults in control circuits must neither cause a machine to start inadvertently or to dangereously move nor prevent a controlled shutdown. The internal SLA4 ground fault dectector makes external ground fault detector modules redundant. The AS-Interface network is monitored by the power supply unit via the AS-Interface cable connected to the various participants. Detected ground faults are stored and signalled via front panel LEDs and relay contacts. The ground fault detector may be manually checked using the test/reset button.


You can place an order for the PULS SLA4.100 AS-Interface® power supply online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.

Specification

Input Data
AC-Input Voltage AC 100-120/220-240V (-15%/+10%)
DC-Input Voltage -
EN61000-3-2(PFC-Norm) fulfilled
Power Factor 0.53
Input Inrush Current Limitation NTC
Output Data
nominal Voltage 30.5Vdc
Adjustment Range 30.6
Output Current Range 4A
Output Current 4A at 30.6V
Output Power 0W
max. Ripple and Noise Voltage 50mVpp
Physical Characteristics
Dimension 65mm x 124mm x 102mm
Weight 620g
Mounting DIN-Rail
Operating Temperature -10°C ... +70°C
General
Derating 3W/° at >+60°C
Efficency, typ. 88.0%
Power Losses, typ. 13.5W
MTBF 1.222.000h
Connection method Screw terminals
E Classification eClass 5.1 27049002, eClass 6.x 27049002, eClass 7.x 27049002, eClass 8.0 27049002, eClass 9.0 27040701, ETIM 4.0 EC000599, ETIM 5.0 EC002540, HS Code HS 85044082
Package Checklist