Description
The MGate MB3660 (MB3660-8 and MB3660-16) gateways are
redundant Modbus gateways that convert between the Modbus TCP and Modbus
RTU/ASCII protocols. They can be accessed by up to 256 TCP master/client
devices, or connect to 128 TCP slave/server devices. Routing through the serial
ports can be controlled by IP address, TCP port number, or ID mapping.
Serial-port routing by designated TCP port and IP address allows access for up
to 4 TCP clients/masters, while routing by ID mapping (slave ID table) allows
access for up to 256 TCP clients/masters. The MGate MB3660 isolation model
provides 2-kV isolation protection suitable for power substation applications.
The MGate MB3660 gateways are designed to integrate Modbus TCP and RTU/ASCII networks easily. The MGate MB3660 gateways offer features that make network
integration easy, customizable, and compatible with almost any Modbus network.
For large-scale Modbus deployments, MGate MB3660 gateways
can effectively connect a large number of Modbus nodes to the same network. The
MB3660 Series can physically manage up to 248 serial slave nodes for 8-port
models or 496 serial slave nodes for 16-port models (the Modbus standard only
defines Modbus IDs from 1 to 247). Each RS-232/422/485 serial port can be
configured individually for Modbus RTU or Modbus ASCII operation and for
different baud rates, allowing both types of networks to be integrated with
Modbus TCP through one Modbus gateway.
You can also find the MGate MB3660-16-2DC model in the Industrial Ethernet Gateways.
Discover industrial automation solutions appropriate to your
needs, and easily inquire about the MOXA MGate MB3660-16-2AC Industrial Ethernet Gateway through our user-friendly website via
one of our Middle East branches (UAE (Dubai), KSA (Al Khobar, Riyadh), and
Oman).
Specification
Ethernet Interface | |
---|---|
Number of Ports | 2 IP addresses |
Speed | 10/100 Mbps, Auto MDI/MDI-X connection |
Connector | DB9 male |
Protocols | Modbus RTU/ASCII Master, Modbus RTU/ASCII Slave |
Serial port specifications | |
RS-232 Signals | TxD, RxD, RTS, CTS, DTR, DSR, DCD, GND |
Number of Ports | 16 |
RS-422 Signals | Tx+, Tx-, Rx+, Rx-, GND |
RS-485-4w Signals | Tx+, Tx-, Rx+, Rx-, GND |
Serial Standards | RS-232/422/485 (software selectable) |
Connectors | DB9 male |
RS-485-2w Signals | Data+, Data-, GND |
RS-485 Data Direction Control | ADDC (automatic data direction control) |
Isolation | - |
Serial Communication Parameters | |
Data Bits | 7, 8 |
Stop Bits | 1, 2 |
Parity | Even, Odd, Space, Mark, None |
Flow Control | RTS/CTS, DTR/DSR, RTS Toggle (RS-232 only) |
Baudrate | 50 bps to 921.6 kbps |
Software | |
Configuration Options | Web Console (HTTP/HTTPS), Device Search Utility (DSU), MCC Tool Telnet Console |
Utility | - |
Network Protocols | ARP, DHCP Client, DNS, HTTP, HTTPS, SMTP, SNMP Trap, SNMPv1/v2c/v3, TCP/IP, Telnet, UDP, NTP Client, RADIUS |
General | |
MTBF | 495,416 hrs |
Power Requirements | |
Input Current | 2 A @ 30 VDC |
Input Voltage | Redundant dual inputs, 100 to 240 VAC (47 to 63 Hz) |
Power Connector | Terminal block (for DC models) |
Physical Characteristics | |
Dimensions | Dimensions (with ears): 480 x 45 x 198 mm (18.90 x 1.77 x 7.80 in), Dimensions (without ears): 440 x 45 x 198 mm (17.32 x 1.77 x 7.80 in) |
Housing | Metal, IP30 |
Operating Temperature | 0 to 60°C (32 to 140°F) |
Weight | 2830 g (6.24 lb) |
Storage Temperature | -40 to 85°C (-40 to 185°F) |
Ambient Relative Humidity | 5 to 95% (non-condensing) |
Vibration | IEC 60068-2-6, IEC 60068-2-64 |
Shock | IEC 60068-2-27 |
Drop | - |
Safety | UL 62368-1, IEC 62368-1 |
EMC | EN 55032/35 |
EMI | CISPR 32, FCC Part 15B Class A |
EMS | IEC 61000-4-2 ESD: Contact: 6 kV; Air: 8 kV, IEC 61000-4-3 RS: 80 MHz to 1 GHz: 10 V/m, IEC 61000-4-4 EFT: Power: 1 kV; Signal: 1 kV, IEC 61000-4-5 Surge: Power: 2 kV; Signal: 1 kV, IEC 61000-4-6 CS: 10 V, IEC 61000-4-8 PFMF |