Description
To achieve current sharing:
- Plug jumper into pos. 'Output parallel use'. This alters the output V/I characteristic to be 'softer' (25V at 0.4A, 24V at 20A). The output voltage can still be adjusted.
- Missing jumper = 'parallel use', i.e. 'soft' characteristic
To be fused with a 16A, B-type 'circuit-breaker' switch based on the usual thermomagnetic overload sensing principle (used anyway to fuse the input lines).
You can place an order for the PULS SL20.111 DIN-rail Power supply online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.
Specification
| Input Data | |
|---|---|
| AC-Input Voltage | AC 100-120/220-240V |
| DC-Input Voltage | - |
| EN61000-3-2(PFC-Norm) | fulfilled |
| Output Data | |
| nominal Voltage | 24Vdc |
| Adjustment Range | 24-28V |
| Output Current Range | 20-17.1A |
| Output Current | 17.1A at 28V, 20A at 24V |
| Output Power | 480W |
| General | |
| Connection method | Screw terminals |
| E Classification | eClass 5.1 27049002, eClass 6.x 27049002, eClass 7.x 27049002, eClass 8.0 27049002eClass 9.0 27040701, ETIM 4.0 EC000599, ETIM 5.0 EC002540, HS Code HS 85044082 |
| Physical Characteristics | |
| Mounting | DIN-Rail |
| Dimension | 220mm x 124mm x 102mm |
| Weight | 2500g |
| Package Checklist | |
| Packaging Unit | 1pc |