Description
Inrush current limiting done with a fixed 15R resistor (not a thermistor) which is bridged after the unit is running, so losses are minimised. That means no reset time even at a warm-start.
Unit is internally fused (fuse not accessible). For external fusing of unit and for input line protection, use circuit breaker with B-characteristic 10A or slower action, or alternatively T10A HBC fuse.
The unit exclusively uses longlife electrolytics, specified for +105°C (cf. ’The SilverLine’, p.2). High reliability, as
- only four aluminium electrolytics and
- no small aluminium electrolytics are used.
You can place an order for the PULS SL20.100 DIN-rail Power supply online via one of our Middle East branches (Dubai/ Oman/Saudi Arabia) and get it delivered at a low cost at a specific time.
Specification
| Input Data | |
|---|---|
| AC-Input Voltage | AC 200-240V |
| DC-Input Voltage | - |
| EN61000-3-2(PFC-Norm) | |
| Output Data | |
| nominal Voltage | 24Vdc |
| Adjustment Range | 24-28V |
| Output Current Range | 20-17.1A |
| Output Current | 17.1A at 28V, 20A at 24V |
| Output Power | 480W |
| General | |
| Connection method | Screw terminals |
| E Classification | eClass 5.1 27049002, eClass 6.x 27049002, eClass 7.x 27049002, eClass 8.0 27049002, eClass 9.0 27040701, ETIM 4.0 EC000599, ETIM 5.0 EC002540, HS Code HS 85044082 |
| Physical Characteristics | |
| Mounting | DIN-Rail |
| Dimension | 220mm x 124mm x 102mm |
| Weight | 1800g |
| Package Checklist | |
| Packaging Unit | 1pc |