Beijer BFI-H3-24-0058-3F12-SN Frequency Inverter
- Output power 2.2 kW
- Output 3x400 VAC, 5.8 A
- Input voltage 3x380-480 VAC
- IP20
- Brand: BEIJER
- Product Code: BFI-H3-24-0058-3F12-SN
Description
BFI H3 includes IP20, IP55, and IP66 inverters for HVAC, maritime, and other industrial applications, and set a new cost-competitive standard for dedicated fan and pump control. Ease-of-use and innovative design combined with robust performance provide powerful flow control and reliability in a compact drive.
Easy World Automation offers the
easiest way to buy the NAME in the Middle East (UAE (Dubai), KSA (Al Khobar,
Riyadh), and Oman) at the lowest price through online inquiring. Our sales
experts will contact you to fulfill all your industrial automation needs.
Specification
Output ratings | |
---|---|
Output voltage | 3 x 400 VAC |
Rated motor current | 5.8 A |
Overload capacity | 110% for 60 seconds, 125% for 3 seconds |
Output frequency | 0 – 250Hz, 0.1Hz resolution |
Input ratings | |
Supply voltage | 380 – 480VAC ± 10% |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Communication | |
Modbus RTU | 9.6 - 115.2 kbps selectable (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | Built-in |
Modbus TCP | , the external option |
Ethernet IP | , the external option |
Profinet IO | , the external option |
Profibus DP(DPV1) | , the external option |
Device Net | , the external option |
CC-Link | , the external option |
CAN open | |
Display | |
Programmable display | |
External OLED display | |
LED display | |
HVAC | |
PID-control | with sleep/wake up functionality |
Spin start | |
Pump dry protection | |
Stir function | |
Motor pre-heat | |
Broken impeller and broken belt detection | |
Automatic cleaning for pumps | |
Bypass control | |
Fire mode | |
Control terminals | |
Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
Inputs | 5 in total, 3 Digital, 2 Analog or Digital, selectable |
Digital inputs | 10-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Relay outputs | Maximum Voltage: 250 VAC, 30 VDC Switching Current Capacity: 6A AC, 5A DC |
Analog outputs | 0 to 10 Volt, 0 to 20mA, 4 to 20mA |
Outputs | 4 total, 2 relays, 2 analog or digital |
Standard compliances | |
Conformance | CE, UL |
Marine approvals | |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Physical Characteristics | |
IP class | IP20 |
Physical size | Size 2 |
Measurements (H x W x D) | 221 mm x 110 mm x 185 mm |
Weight | 1.8 kg |
Built in Main switch, control switch and potentiometer | |
Conformal coated PCBs | |
Operation temperature | -10 to 50 °C |
Humidity | 95% max, non-condensing |
General | |
EtherCAT Master | , the external option |