Beijer BFI-E3-12-0043-1F12 Frequency inverter
- Output power 0.75 kW
- Output 3x230 VAC, 4.3 A
- Input voltage 1x200-240 VAC
- IP20
- Brand: BEIJER
- Product Code: BFI-E3-12-0043-1F12
Description
BFI E3 inverters offer general-purpose drive facilities, dedicated to low-power applications, combining innovative technology, reliability, robustness, and ease of use. Dust-tight and ready for wash-down, the IP66-rated inverters can be mounted directly on your processing equipment. The IP20-rated inverters can be mounted in control cabinets or machine parts providing the required protection.
You can explore our range of
products and enquire about the Beijer BFI-E3-12-0043-1F12 Frequency inverter for your industrial automation needs. Our
sales experts will pave the way to buy at the lowest price in Dubai, UAE, Saudi
Arabia, Oman, and the Middle East.
Specification
Output ratings | |
---|---|
Output voltage | 3 x 230 VAC |
Rated motor current | 4.3 A |
Overload capacity | 150% for 60 seconds, 175% for 2,5 seconds |
Output frequency | 0 – 500Hz, 0.1Hz resolution |
Input ratings | |
Supply voltage | 200 – 240VAC ± 10% |
Supply frequency | 48 – 62Hz |
Power cycles | 120 per hour maximum, evenly spaced |
Communication | |
Modbus RTU | 9.6 - 115.2 kbps selectable (8N1, 8N2, 8E1, 8O1) |
BACnet MS/TP | |
Modbus TCP | |
Ethernet IP | |
EtherCat | |
Profinet IO | |
Profibus DP(DPV1) | |
Device Net | |
CC-Link | |
CAN open | |
Display | |
Programmable display | |
Multi language OLED display | |
External OLED display | |
LED display | |
HVAC | |
PID-control | PI-control with sleep/wake up |
Spin start | |
Pump dry protection | |
Stir function | |
Motor pre-heat | |
Broken impeller and broken belt detection | |
Automatic cleaning for pumps | |
Bypass control | |
Fire mode | |
Control terminals | |
Power supply | 100 mA @ 24 VDC, 20 mA @ 10 VDC |
Inputs | 4 in total, 2 Digital, 2 Analog or Digital, selectable |
Digital inputs | 8-30 V DC, PNP, Response time: < 4 msec, Internal or external supply |
Analog inputs | Resolution:12 bit, Response time: <4 msec; Accuracy: <± 2% of full scale, Adjustable scaling |
Digital transistor outputs | 24VDC/20 mA, Internal supply |
Analog outputs | 0 to 10 V, 10 to 0 V, 0 to 20mA, 20 to 0mA, 4 to 20mA, 20 to 4mA |
Outputs | 2 total, 1 relay, 1 analog or digital |
Standard compliances | |
Marine approvals | |
Earth leakage current | EN 61800-5-1: 2007. Test techniques EN 60990:2000. 1x230 VA < 2,5 mA, 3x400VAC < 4,65 during runing |
Dielectric strength | 61800-5-1: 2007 |
Surge | EN 61800-3: 2004+A1-2012. Test techniques EN 61000-4-5:2006. |
Physical Characteristics | |
IP class | IP20 |
Measurements (H x W x D) | 173 mm x 83 mm x 123 mm |
Weight | 1.0 kg |
Built-in EMC-filter | |
Conformal coated PCBs | |
Operation temperature | -10 to 50 °C |